| MODEL |
R1500-48 R1500-48S |
R1200-24 R1200-24S |
| PRODUCT STATUS |
Available |
December 2000 |
| OUTPUT |
| Voltage |
230VAC ± 5% |
| Load regulation |
± 5% 0-130% load |
| Frequency |
50Hz/60Hz ± 0.02% |
| Distortion |
<3% THD for linear load |
| Load power factor |
0.6 lagging to 0.8 leading |
| Nominal output power at 50°C |
1500VA |
1200VA |
| Efficiency |
90% (>75%@100VA) |
88% (>75%@100VA) |
| Surge capability (programmable to suit input protection) |
240% for 1sec, 200% for 5sec, 130% for 1 minute (typical at 30°C, thermally limited)
|
| INPUT |
| Voltage range |
40-58V |
20-29V |
| Low voltage shutdown |
43.5V (adjustable) |
21.7V (adjustable) |
| Nominal full load input current |
31A at 48V |
50A at 24V |
| Maximum continuous input current (programmable to suit circuit protection) |
40A |
55A |
| Inrush current |
< 30A |
| No load power draw |
< 14W |
| Sleep mode (output disabled) |
< 1W |
| Reverse voltage protection |
Automatic, indefinite |
| ISOLATION |
| Input to output |
3kV RMS |
| Input to case |
500V DC |
| ALARMS CONTROL AND COMMUNICATION |
| Alarm output |
Volt free changeover contacts |
| Low battery output |
Open collector 60V 20mA max |
| Remote control input |
Remote On/Shutdown control |
| External sync input |
45Hz to 65Hz |
| Remote metering / data logging |
365 days via FPD Power Management Unit or RS232 serial adaptor SA100
|
| System configuration settings |
DIP switch or via FPD Power Management Unit PMU100 (two level secure access) |
| Remote control and diagnostics |
Via FPD Power Management Unit PMU100 using RS232 or open collector parallel outputs |
| ENVIRONMENTAL |
| Operating temperature range |
-15°C To +50°C |
| Cooling |
Temperature controlled fan |
| Ingress protection |
IP20 |
| COMPLIANCE AND APPROVALS |
| Safety |
BS EN 60950 |
| Emissions |
BS EN 50081-1 |
| Noise immunity |
BS EN 50082-2 |
| PHYSICAL |
| Dimensions including mounting flanges |
250 X 342 X 95 (H x W x D) |
| Weight |
5kg |
| DC input connections - standard |
55A Anderson (standard cable size 10mm² or 16mm²) |
| DC input connections - stud option (S suffix) |
8mm studs for cable size up to 95mm² |
| AC output connections |
Shrouded Wieland type ST18 16A |
| Monitoring/control connections |
RJ45 |